Yeah, sorry, not very precise. I have 3 wires coming from the light (red, blue, black) and 2 wires coming from the ceiling (red and blue). Connecting blue to blue and red to red lights up one bulb. If I add the black wire on either side, I get 2 or 3 bulbs to light up, never 5.
Sounds like you need to connect the red and blue from the lamp to one of the house wires and the black from the lamp to the other house wire.
Alrighty then. I'm not familiar with anything but Danish electrical building codes, so have that in mind when reading the following. In newer Danish installations red would be the switched wire and blue neutral. But that assumes that building codes were followed, sometimes DIY'ers will mess it up and leave you with a potentially dangerous situation.
I saw the other comment about how you could end up with parts of the lamp being shorted to 230V if you don't know what you're doing. I wouldn't be so afraid any longer, if that happened you would have felt it by now ;-) besides we don't have a history of connecting anything but protection earth to the metal part of any device, and with lamps that's only done if it's designed to be used in a damp environment, like a bathroom or outdoors.
I suspect that the lamp is wired so that the blue wire is neutral and connected to all the sockets, red and black are connected to 2 and 3 sockets respectively. That would allow you to turn on either 2, 3, or 5 bullbs. But it is just extremely hard to diagnose with text and pictures only.
If you disconnect and unmount the lamp, and then take a look at the sockets in the lamp. Can you tell which wires goes where?
Do you have a way of measuring continuity? Like a multimeter?
Have you tried switching bulbs around? Maybe some are burned out?
Thanks a lot for taking the time to go be me so much information.
I started with switching the bulbs and that's all right
Having no ground wire coming from the ceiling, I am definitely not going to attach any wire to the body of the light.
I think I will try to attach the blue wire on one side and red and black together on the other side, maybe it will work ?
I could disassemble the light to inspect which wire goes to which socket but I'm not sure I could put it back together again.
Anyway, thanks a lot
Don't mention it. It's a mental challenge for me to diagnose this problem with only text. And I like a challenge.
Just to make sure, you have 5 sockets AND 5 known good bulbs? Ie you are sure that all bulbs are working?
Maybe. I'm fairly certain that the lamp is wired such that
The question is just, which wire is which?
I've seen black used for neutral in a 1950s installation in DK.
If you're up for it, I propose that you test it systematically. We need to figure out which wire need to be separate from the others. Start by enumerating the bulbs.
I'm going to shorten the names of the wires, lr, lba, and lbu. L for lamp, r for red, ba for black, and bu for blue. Same for ceiling wires, cr and cbu.
Which bulbs light up when you attach
I'll bet that in one of these cases all the bulbs will light up. And that will be the way to wire the lamp up.
If none of the three combinations lights up all bulbs, then either the lamp is faulty, or my own bulb is :-)
Issue is I can't see any color for the ceiling wires (only one or two cm of wire, hooked directly into the connector), so I'll use C1 for ceiling one and C2 for ceiling 2. Lba makes the switch:
I don't think switching c1 and c2 will make any difference.
I am wondering if black shouldn't go to both ceiling wires...
Definitely get lba connected to one wire, and lbu and lr to the other. Lba is the common wire, get that alone and all the bulbs will light up.
Differences between the wires in the ceiling is that one is switched live and the other is neutral.
It may be pedantic, but lba connects to the side of the sockets, which is more easy to touch. That's why I would connect that to neutral. But if you can't see the wires in the ceiling, then it doesn't matter that much.
We're on my friend! Cheers!
And there was light :-)
I'll try just that and update